TEST REPORT

 

NO. 960840750-3 of 05 APRIL 2006

 

 

FLAME SPREAD TEST

 

Material Tested: Kryptaglow Luminescent Paint Layer on Cement Board identified by Co-Leash Inc. as consisting of three

coats: (i) Kryptaglow White Latex Base Coat # 1171, (ii) Kryptaglow Paint MEA Special Blend # 1300A,

and (iii) Kryptaglow Clear Protective Top Coat # 1102, and listed in this test as Material A.

 

 

FLAME SPREAD DATA

____________________________________________________________________________________________________

 

T e s t P a r a m e t e r s Flame Spread Flame Spread

No. Material Temperature Specific Temp. Factor, Fs Index, Is * Comments

Drop, ΔT, K Rise, β, K/kW dimensionless dimensionless

____________________________________________________________________________________________________

 

 

1 Material A 40.7 32.3 2.04 20.4 Ignites with

difficulties

____________________________________________________________________________________________________

* The data on Fs and Is are the mean from the test on four specimens of the material tested.

 

CONCLUSION:

 

The tested samples of Material A meet the requirements of NYC BC Ref. Std. RS6-1A, para. 5.1.2.

 

 

 

TEST DESCRIPTION

 

1. The test per NYC BC Ref. Std. RS6-1A, para. 5.1 - 5.2 and ASTM E162. Ambient test conditions: T=22°C, RH=40%,

P=101.2 kPa.

 

2. The sides of the test specimens were wrapped with aluminum 0.05-mm foil. The specimens were conditioned before the

test for 24 hours at 60°C with following conditioning at the above listed ambient test conditions for 24 hours. Test

exposure time for each of the specimens tested - 15 min after each of the initial ignitions.

 

(continued on page 2)

 

CIEMS TEST REPORT NO. 960840750-3 of 05 APRIL 2006

 

Page 2 of 2

 

 

3. The experimental error evaluated by the partial derivatives and least squares methods does not exceed 7%. The data on the

standard deviation are kept on file at CIEMS.

 

4. INSTRUMENTS AND DEVICES USED

- Flame Spread Testing Device Model 394-19DI BD

- Radiation Pyrometer Model ST-30 Raynger

- Optical Pyrometer Model MX-2 Raytek

- Moseley X-Y Recorder Model 7035B HP

- Digital Timer Model Labchron-1402 LLI

- Programmed Temperature/Humidity Controller Model 100 HM

- IR Thermometer Model IR550 DKS

- Precision Potentiometer/Thermometer Model 8659-AZ L&N

- Microscopes: Model 9700 TSL, Model 500 PH, Model Tukon-300 Wilson

- Precision Micrometer Model 25/100 Krupp/Hommelwerke

- Starrett Dial Indicator Model 25-109 (1.27 µm/div)

- Digital Hygrothermometer Model 63-844 MI, Barometer Model 602650 SB.

 

5. Reference material used for the comparative measurements and for the test setup calibration:

- NIST SRM 1002 (Is=153, Q=36.5).

 

6 The equipment used in the test meets the applicable NIST, ASTM, ASME, OSHA and State requirements and was

calibrated with the standards traceable to the NIST. The calibration was performed per ANSI/ASQC M1-1996,

ANSI/ISO/ASQ Q9004-2000, ISO 10012:2003, ISO 5725-2:1994, MIL-STD-45662, MIL-I-45208, NAVAIR-17-35-

MTL-1, CSP-1/03-94, and the instruments manufacturers' specifications.

 

7. The equipment passed a periodic accuracy test in June 2005. Next test - June 2006. The linear and angular measure

equipment and weights will be calibrated in December 2005.

 

 

TEST ENGINEER: 29

 

DIVISION MANAGER: Cynthia Smythe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 